PRESSURE TRANSDUCERS - INSTALLATION AND USE
INTRODUCTION
Common problems or questions concerning the use of pressure transducers
are:
1. Transducer outputs and their wiring configurations;
2. Wiring one transducer to multiple readouts, recorders, computers,
etc.;
3. Wiring multiple transducers to one readout, recorder, computer, etc.;
4. Using a milliamp signal with voltage input instrumentation;
5. Determining how many transducers can be excited from one power supply.
Each of these problems, or questions are discussed in detail in the following article.
TRANSDUCER OUTPUTS AND THEIR WIRING CONFIGURATIONS
OMEGADYNE transducers have three main types of electrical outputs; millivolts
(mV), volts (V), and current (mA). It is important for the user to know
which output suits his application to ensure proper selection of a transducer.
The following will describe the advantages, disadvantages, and wiring for
millivolt, volt and current output transducers.
Transducers with a millivolt output are generally used in laboratory
applications. They are low cost, small in size, and require a regulated
power supply. Remembering that the millivolt signal is very low level, it
is limited to short distances (up to 200 feet is usually considered the
limit) and is very prone to stray electrical interference from other nearby
electrical signals (other instrumentation, high ac voltage lines, etc.).
Typical wiring configurations are shown in Figure 1.
Transducers with an amplified voltage output are generally used in a
light industrial environment and computer interface systems, where a higher
level dc signal is required. Due to the built-in signal conditioning, they
are higher cost and larger in size than the millivolt output transducers.
Amplified voltage signals can travel up to medium distances and are much
better in their immunity to stray electrical interference than the millivolt
signal. Typical wiring configurations are shown in Figure 2.
Transducers with a current output are generally used in heavy industrial
environments, and are the most common type used in process control. Transducers
with a current output are generally called transmitters. The difference
between a transducer and a transmitter is a commonly asked question.
A transducer produces millivolts, amplified voltage, or current output.
A transmitter produces current output only. Again, due to the built-in signal
conditioning, the transmitters are higher cost and larger in size than the
millivolt output transducers. Unlike the millivolt and voltage output transducers,
a current signal is immune to any stray electrical interference, a valuable
asset in the factory. A current signal also can be transmitted long distances.
Typical wiring configurations are shown in Figure 3.
Amplified Current 2 Wire Interface Cick Here for Cabling/Wiring Details
Amplified Voltage 4 Wire Interface - Cick Here for Cabling/Wiring Details
WIRING ONE TRANSDUCER TO MULTIPLE READOUTS, RECORDERS, COMPUTERS, ETC.
One of the great advantages of a current signal is the simplicity in
setting up a multi-instrument system. Long distance transmission from instrument
to instrument without electrical interference make multi-instrument systems
easy. For example, a material test center may have one control room for
all the different test labs, enabling operation from one central location.
Instrument calibration and troubleshooting are simple in a multi-instrument
current loop. The only limitation for the number of instruments is the amount
of voltage from the power supply driving the current loop. The minimum voltage
required is determined by Ohms law, V-IR (voltage equals current times resistance).
This is shown and explained in Figure 4.
WHERE:
RLINE = resistance due to wire
RLOAD = combined instrumentation resistances
VsTRANSDUCER = minimum supply voltage for transducer
For example, let's assume you have the following:
1. Pressure transmitter (4-20 mA) with 12-30 Vdc supply voltage;
2. Panel meter with a 10 ohm input impedance;
3. Recorder with a 25 ohm input impedance;
4. Computer with a 200 ohm input impedance;
5. Lead wire resistance of 5 ohms.
Minimum voltage required = (.020). (5 + 10 + 25 + 200) + 12 = 16.8 volts. 24 volts is the most common power
supply in a 4-20 mA current loop. Wiring a voltage or millivolt signal to
multiple instruments also can be done, but is not as easy and does not have
the calibration and troubleshooting advantages inherent in a current loop
system. The voltage or millivolt signal can be wired in parallel to multiple
instruments as shown in Figure 5. This method assumes a very high input
impedance in the instruments being wired. If this is not the case, an analog
output can be used instead to retransmit the signal.
WIRING MULTIPLE TRANSDUCERS TO ONE READOUT, RECORDER, COMPUTER, ETC.
In measuring multiple pressures, it is a common mistake trying to use
multiple transducers, a switching device, and just one panel meter, thus
saving money on multiple panel meters (or any other instrumentation). The
problem is that each transducer has a unique zero point and the readout
only has one zero screw. The net result is that the total accuracy increases
to about 3%, even though each sensor is 0.5% accurate. In most cases, this
larger error is intolerable.
The correct method of using multiple transducers with one readout device
is to use transducers that have built-in zero and span adjustments screws,
the same output (voltage or current), and the same pressure range. Each
transducer is adjusted by applying a known pressure, so that they all have
identical outputs. When they all have identical outputs, the meter is scaled
and a switch can be used.
Another solution to using multiple transducers with one readout is to
use a scanner instead of meter and a switch. There are many types of scanners.
The type of scanner that works with multiple pressure transducers must have independent scaling
on each channel.
Some scanners, besides having independent scaling on each channel, also
offer independent current, voltage, or millivolt inputs to each channel.
These types of scanners enable you to use transducers with different outputs
as well as different pressure ranges with the same instrument.
USING A MILLIAMP SIGNAL WITH VOLTAGE INPUT INSTRUMENTATION
Most instrumentation is set up to receive voltage. A commonly asked question
is how to use a current signal with instrumentation set up for voltage.
This is simply done by installing a resistor across the input terminals
of the instrumentation. The value of the resistor is determined by Ohms
law (V = IR). For example, installing a 500 ohm resistor will convert 20
mA to 10 volts (V = IR = .020 x 500). This is shown in Figure 7. The only
other consideration is the zero offset. Since most current loops have a
low end of 4 mA, there will be a zero offset. Using the same value resistor
as above 4 mA will convert to 2 volts.
|
R=V/I
|
Where:
|
R = Size of Resistor
V = Desired Voltage
I = Current
|
|
Example:
|
| To Convert 4-20 mA into 2-10 V |
| R = V/I = 10/.02 = 500 Ohms |
A 500 Ohm Resistor Would be Installed Across the (+) and (-) Terminals
on the Instrumentation
|
DETERMINING HOW MANY TRANSDUCERS CAN BE EXCITED FROM ONE POWER SUPPLY
Multiple transducers can be excited from one power supply. The number
of transducers that can be used is simply determined by the current draw
of each transducer and the current capacity of the supply source. The sum
of the current draw of the transducers can not exceed the total current capacity of the supply.
For example, if you have 50 transducers drawing 13 milliamps, you will need a power supply having at least 650 milliamps
(50 x 13). There is also nothing wrong with powering just one transducer
with a power supply having high current capacity.
Discription of Illustrations:
Figure 1. Typical wiring configuration for millivolt output transducer
Figure 2. Typical wiring configuration for voltage output transducer (-excitation and -signal are common)
Figure 3. Typical wiring configuration for current output transducer
Figure 4. Multi-instrument 4-20mA current loop (panel meters, chart recorder, computers, etc.)
Minimum voltage req'd = (0.20 Amps)(R LINE + R LOAD) + Vs TRANSDUCER
Figure 5. Multiple instruments wired in parallel to a voltage
output transducer
Figure 6. Multiple transducers wired to one meter and one switch (transducers
with built-in zero & span adjustments, same outputs & same pressure
ranges)
Figure 7. Converting current into voltage for instrumentation set up for voltage
|
HANDLING, LOCATING AND INSTALLING TRANSDUCERS
A. Diaphragm - Do not press or touch the diaphragm as you may damage
or alter its calibration, particularly on low pressure range models.
B. Fittings and Hardware - Use appropriate pressure rated fittings and hardware. Make sure you have
the correct thread type and size fitting. Use pressure limiters, capacity
chambers, snubbers, etc., if needed.
C. Operate at Ambient Temperatures - Locate the transducer where it can be readily inspected and serviced.
Ambient temperature should be within the transducer specifications. The temperature coefficient effects on the overall accuracy of the transducer
can be minimized the closer the ambient temperature is to 25°C. Avoid
locations with excessive vibration.
D. Installation - Installation should be made only by qualified personnel
familiar with safety practices and knowledgeable with all industry accepted
standard relating to pressure systems.Transducer calibration and/or zero may shift if it is over-torqued when
installing. Check for a zero shift after installing. When installing transducers, refer to standard industry torque data for
thread size and material type .
|
|